Advanced Search
Surplus Record

BOILERS, FIRETUBE

400 HP Cleaver-Brooks, 150 psi, gas, firetube boiler, 2001

Request a Quote
Share
400 HP Cleaver-Brooks, 150 psi, gas, firetube boiler, 2001
Nationwide Boiler's low NOx, 400 hp (13,800 lbs/hr) Cleaver Brooks skid-mounted firetube boiler is designed at 150 psig pressure, firing natural gas. It is fully piped and wired and includes the following components:

400 hp 4-Pass Dryback Firetube Boiler
Low NOx Burner
Gas Pressure Regulator
Complete Gas Train
Control Panel
Valve Trim (safeties, blowdown, etc.)
Low Water Cutoffs
Modulating Feedwater Control Valve
Steam Pressure Gauge
Meets FM / IRI / NFPA 85
EconoStak Economizer (optional)
Ultra Low NOx CataStak SCR System (optional)
Operating Manuals

Fuel Consumption:      
Natural Gas:      16,800 SCFH @ 2-10 psig
      
Connection Sizes:      
Main Steam:       6"-300# FLG
Natural Gas:       4"-150# FLG
Blowdown / Drain:       2" NPT
Feedwater:       2½" NPT
Chemical Feed:      1" NPT
Water Column:      ¾" NPT
Flue Outlet:      24" OD
      
Electrical Power Service Requirements:       
460 VAC, 3 ph, 60 hz, 20 amp
      
Dimensions & Weights:       
Length:      17' 2"
Width:      10' 1"
Height:      11' 2"
Shipping Weight:      36,570 lbs
Operating Weight:      51,380 lbs
      
Emissions Data (natural gas):
NOx (corr. to 3% O2):      60 ppm
CO (corr. to 3% O2):      50 ppm

Surplus Record Surplus Record, Inc., an Ariba Company. All Rights Reserved.
http://www.surplusrecord.com
Tel: 312-372-9077        Customer Service        Mobile Apps        Advertise