GENERATORS, A.C., DIESEL ENGINE DRIVEN, 60 CYCLE
600 KW Cat #XQ600, C18, 1800 RPM, S/A, 20'container, 3 ph, 208/240/480 V., Tier 2, 2006
Request a Quote
Share
718333.jpg 718333a.jpg 718333b.jpg 718333c.jpg
XQ600
SOUND ATTENUATED POWER MODULE
60 Hz


FEATURES

EMISSIONS
EPA and CARB Emissions Certified for non-road mobile applications.

CAT® DIESEL GENERATOR SETS
Factory designed, certified prototype tested with torsional analysis. Production tested and delivered to you in a package that is ready to be connected to your fuel and power lines. Electric Power Design Pro computer sizing available. Supported 100% by your Caterpillar dealer with warranty on parts and labor. Extended warranty available in some areas. The generator set was designed and manufactured in an ISO 9001 compliant facility. Generator set and components meet or exceed the following specifications: AS1359, AS2789, ABGSM TM3, BS4999, DIN6271, DIN6280, EGSA101P, JEM1359, IEC 34/1, ISO3046/1, ISO8528, NEMA MG1-22.


CATERPILLAR® SR4B GENERATOR
Single bearing, wye connected, static regulated, brushless permanent magnet excited generator designed to match the performance and output characteristics of the Caterpillar diesel engine that drives it.

RELIABLE, FUEL EFFICIENT DIESEL
The compact, four-stroke-cycle diesel engine combines durability with minimum weight while providing dependability and economy. The fuel system operates on a variety of fuels.

CATERPILLAR® COOLING SYSTEM
Sized compatible to rating with energy efficient fan and core.

CATERPILLAR® SWITCHGEAR
Single unit or optional paralleling components. Circuit breakers, bus bars, and connection panel ready to connect.

EXCLUSIVE CATERPILLAR® VOLTAGE REGULATOR
Three-phase sensing and adjustable Volts-per-Hertz regulation give precise control, excellent block loading, and constant voltage in the normal operating range.

SOUND ATTENUATED ISO CONTAINER For ease of transportation and protection. Meets 70 dBA at 50 ft or below per SAE J1074
measurement procedure.


FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT
System       Standard      Optional
Engine       Air cleaner, with service indicator
Batteries
Battery charger, heavy duty
Charging alternator
Filters; fuel, RH with service indicators; lubricating oil
Fuel-water separator system
Insulated muffler
Pump, fuel priming — RH Radiator
Service meter
Standard jacket water heaters with service valves
Sump pump
Governor
2301A load share governor      Fuel transfer system
Oil level makeup system
Special radiators for high or low ambients
Sump pump — RH
Generator      SR4B brushless, 480 volt, PM excited three-phase with digital voltage regulator, space heater      Mil Std 461B, VDE 875 Level N Temperature rise detectors
Containerized
Module      Air intake louvers
Bus bar access door
Fuel tank w/gauge — 2500 L (660 Gal) UL listed
Steel deck floor — galvanized
24 VDC lighting
Sound attenuated (66 dBA @ 50 ft)      Fuel transfer/double wall
Motorized louvers
110 VAC lighting
Undercarriage
Bottom load cable access
Switchgear      Generator mounted EMCP II
Automatic start/stop with cycle cranking and cooldown timer
Auxiliary power connections for jacket water heater, battery charger, space heaters
Battery charger, heavy duty 20A Circuit breaker, manually operated Connection terminals, 3-phase and neutral Synch lights and reverse power relay      


SPECIFICATIONS

CAT SR4B GENERATOR
Type ...... Static regulated brushless PM excited Construction ...... Single bearing, close coupled
Three-phase ........... Wye connected — 6 lead
Insulation ........... Class H — 2 extra dips and bakes on random wound units
Enclosure ........................... Drip proof Alignment ........................... Pilot shaft
Overspeed capability ..................... 130%
Voltage regulator .......... 3-phase sensing with Volts-per-Hertz
Voltage regulation .............. Less than ± .05%
Voltage gain ...... Adjustable to compensate for engine speed droop and line loss
Wave form .............. Less than 5% deviation
TIF................................ Less than 50
THD.............................. Less than 3%

CAT® 3412 ENGINE
V-12, 4-stroke-cycle diesel
Bore — mm (in) ..................... 137.2 (5.4) Stroke — mm (in) ..................... 152.4 (6)
Displacement — L (cu in) .............. 27 (1649) Aspiration ............ Turbocharged-Aftercooled


TECHNICAL DATA

Power Rating
60 Hz      ekW      Standby       Prime
600      545
Engine and Container Information
Engine Model
Container size      m (ft) Container dimensions      
3412
12 (40)
see below
Fuel Capacity Hours of Operation at 60% Load Factor
2500 L (660 Gal)       hours      

13      15
Approximate Weight (Dry) — Container with Generator Set
Including Container       kg (lb) With Undercarriage      kg (lb)      

13 850 (30,500)
16 800 (37,000)




Container Dimensions

12192.0 [480.00]



R1219.2 [R48.00]
2 Places






2438.4 [96.00]





R963.3 [R37.92]
3 Places
R744.5 [R29.31]
2 Doors Each Side
(Cable Storage Box)
12192.0 [480.00]

7723.5 [304.07]

1877.2 [73.90]

4115.0 [162.01]


The power module must have support under the center when set

Dimensions
Length      12192.0 mm       480.00 in Width       2438.4 mm       96.00 in Height       4115.0 mm       162.01 in



STANDARD CONTROLS
12 m (40 ft) CONTAINERS
480V/60 Hz

ELECTRONIC MODULAR CONTROL PANEL (EMCP II) COMPONENTS

GENERATOR SET CONTROL (GSC)
Monitoring
Sequentially rotating, backlit LCD display of engine hours, engine rpm, DC battery voltage, oil pressure, and water temperature. Includes pushbutton to hold display on any single parameter.
Protection
Shutdowns:
Overspeed, overcrank, high water temperature, low oil pressure, and emergency stop. With LED indicator for each condition.
Alarms:
Low coolant level
AC Metering
Three-phase volts (L-L), amperes and frequency with phase select pushbutton, on backlit LCD. Metering accuracy is
0.5%.
Control
Automatic starting with field adjustable cycle crank, failure to start (overcrank), and cooldown timer.
Programming and Diagnostics
Includes field programmable set-points for engine control and monitoring variables and self diagnosis of EMCP II system component and wiring failures.

ALARM MODULE
Flashing LED warnings for: low coolant temperature, high coolant temperature (pre-alarm), low oil pressure (pre-alarm),
engine control switch not in automatic, and low DC voltage. Includes alarm horn and acknowledge pushbutton.

ENGINE CONTROL SWITCH
Snap action rotary switch, four-position — off/reset, automatic, manual, stop/cooldown. Off/reset for engine shutdown and resetting faults, automatic for remote starting by customer contact closure, manual for local starting and manual paralleling, stop/cooldown for manual operation cooldown.



ALARM ACKNOWLEDGE/LAMP TEST SWITCH
Three-position, spring return to center switch for alarm acknowledge and lamp test of all discrete indicating lamps. Lamp test shall also sound the alarm horn.

ANNUNCIATION CIRCUITS
Upon receipt of an alarm or shutdown condition, the horn shall sound and an LED shall flash. Upon acknowledgement from alarm acknowledge/lamp test switch, the horn shall be silenced and the lamp steadied. LED shall be extinguished when ECS is placed in the off/reset position if the alarm condition has been corrected.
Circuits are recurring such that the LED shall flash and the horn sound, should another fault occur even prior to correction of the initial fault.

EMERGENCY STOP PUSHBUTTON Mushroom head, twist to reset, causes engine shutdown and tripping of the
generator circuit breaker. Prevents engine
starting when depressed.

MANUAL PARALLELING
Controls consisting of reverse power relay, synchronizing lights, and switch. Reverse power condition causes tripping of the generator circuit breaker, immediate
engine shutdown, flashing of indicating lamp, and sounding of alarm horn.

GENERATOR MOUNTED CIRCUIT BREAKER Fixed mounted, three-pole, manually operated, molded case circuit breaker with
solid state trip unit for overload (time
overcurrent) and fault (instantaneous) protection. Includes DC shunt trip coil activated on any generator set monitored fault. Circuit breaker is sized for full load capacity of the generator set at 0.8 power factor.

LOAD SHARE GOVERNOR
Electronic load sharing governor with speed adjust potentiometer, idle/rated switch, and isochronous/droop switch.

VOLTAGE REGULATOR
Standard Caterpillar generator-mounted digital voltage regulator with voltage adjust rheostat.


STANDARD CONTROLS
CURRENT TRANSFORMERS (3)
Five-ampere secondary with shorting terminal strips

POTENTIAL TRANSFORMERS (3)
120 VAC secondary with primary and secondary fuse protection, two connected to the generator side of the circuit breaker, one connected to the load side of the circuit breaker.

BUS BARS
Three-phase plus fully rated neutral bus bars with NEMA standard hole pattern for connection of customer load cables and generator cables. Bus bars are sized for full load capacity of the generator set at 0.8 power factor. Also includes ground bus, connected to the generator frame ground and container frame with holes for connection of field ground cable. Bus bars are accessible from outside of the power module via hinged, lockable cable access door.


ACCESSORY POWER
3400 Power Modules
Three 120 VAC (60 Hz units) shore power connections for jacket water heaters, generator space heater, and battery charger.

BATTERY CHARGER
24 VDC/20A battery charger with float/
equalize modes and charging ammeter.


www.CAT-Eiectr icPower.com


U.S. sourced


© 2000 Caterpillar