TRANSFORMERS, THREE PHASE, 60 CYCLE

5250 KVA 13200 Pri. 4160/2400 Sec., General Electric, taps, fan cooled

Request a Quote
Share
5250 KVA 13200 Pri. 4160/2400 Sec., General Electric, taps, fan cooled
(One) 5250KVA continuous, 65°F Rise, General Electric Class OA/FA, 3 phase, 60 cycle Transformer. Primary voltage rating 13,200V Delta. Secondary 4160/2400V Wye, 722 Amps at 4160V, 55/65°C forced air. Two (2) 21/2 taps above and below. 5.50% impedance, equipped with 7 fans with motors, equipped with dial position tap changer, filled with 880 Gallons of Type Number 1 oil, filler gauge, temperature indicator, metering and top bushings. S/N: H881108. Manufactured in 1982.

Approximate Dimensions:
84"L X 101"W X 133"H

Approximate Shipping Weight:
22,300 Lbs.

Untanking:
9,700 Lbs.

Tank And Fittings:
6,000 Lbs.

Type 1 Oil 880 Gal:
6,600 Lbs.